1.1 All previous defects and non-conformances attended to and recorded
Pass
Fail
1.2 Inform Flinders Ports signal tower and SAMFS of testing being carried out
*
Completed
1.3 Isolate Romteck unit
*
Completed
1.4 Check for any obstructions to pump, control panel or driver access
*
Pass
Fail
1.5 Check for signs of damage or corrosion
*
Pass
Fail
1.6 Check for signs of oil and water leakage
*
Pass
Fail
1.7 Check battery containment / covers and coupling guards
*
Pass
Fail
1.8 Check pump controllers are on and not isolated or in alarm
*
Pass
Fail
2.1 Float voltage - Pump 1 starter battery
*
2.2 Float voltage - Pump 2 starter battery
*
2.3 Float voltage - Pump 1 controls battery
*
2.4 Float Voltage - Pump 2 controls battery
*
2.5 Remove ship-to-shore hydrant caps and open V18 & V19
*
Completed
2.6 Start Pump 1 and measure voltage while cranking
*
2.7 Check "Pump Running" light for Pump 1 is on within 10 seconds
*
Pass
Fail
2.8 Start Pump 2 and measure voltage while cranking
*
2.9 Check "Pump Running" light for Pump 2 is on within 10 seconds
*
Pass
Fail
3.1 Pump 1 at 0 L/min
*
3.2 Pump 1 at 1,500 L/min
*
3.3 Pump 1 at 2,500 L/min
*
3.4 Pump 1 at 3,500 L/min
*
3.5 Pump 1 at 4,500 L/min
*
3.6 Pump 1 at 5,000 L/min
*
3.7 Pump 1 at 5,500 L/min
*
3.8 Pump 1 Bearings temperature
*
3.9 Pump 2 at 0 L/min
*
3.10 Pump 2 at 1,500 L/min
*
3.11 Pump 2 at 2,500 L/min
*
3.12 Pump 2 at 3,500 L/min
*
3.13 Pump 2 at 4,500 L/min
*
3.14 Pump 2 at 5,000 L/min
*
3.15 Pump 2 at 5,500 L/min
*
3.16 Pump 2 Bearings temperature
*
3.17 At the conclusion of flow tests close V18 & V19 and replace ship-to-shore hydrant caps
*
Completed
4.1 Inspect oil filters and replace if necessary
*
Completed
4.2 Inspect air filters and replace if necessary
*
Completed
4.3 Inspect fuel condition and replace fuel filter if necessary
*
Completed
4.4 Inspect cooling system hoses and replace if necessary
*
Completed
4.5 Flush cooling system and replace with coolant approved by manufacturer
*
Completed
4.6 Pressure test cooling system as per manufacturer's recommendations
*
Completed
4.7 Clean Y Strainer on water side of heat exchanger
*
Completed
4.8 Check drive coupling for wear and lubricate
*
Completed
4.9 Check hold down bolts and tighten if necessary
*
Completed
4.10 Check exhaust system for corrosion and leaks
*
Completed
5.1 Replace fire pump batteries
Completed
5.2 Check all pressure gauges calibration
Completed
6.1 Disassemble each pump and valves as per AS 1851 Table 3.4.3.9 & 11
Completed
7.1 Check valves are in their correct standby position (see wall chart)
*
Completed
7.2 Check fire pumps have stopped and low fuel alarm has not operated
*
If either low fuel alarm is active arrange for both fuel tanks to be filled
Pass
Fail
7.3 Advise SAMFS works are completed and de-isolate Romteck unit
*
Completed
System Failures & Comments
Defect Type: 1 - Critical Defect, 2 - Non-Critical Defect, 3 - Non-Conformance, 4 - Recommendation
Service Person Name
*
First Name
Last Name
Licence No. and Licence Type / FPAS No.
*
Name of Service Provider Company
*
Phone
*
(###)
###
####
Email